Siemens SIMATIC S7-1500 Buffer Copy without Checking Size of Input (CVE-2021-3177)

critical Tenable OT Security Plugin ID 504235

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Python 3.x through 3.9.1 has a buffer overflow in PyCArg_repr in
_ctypes/callproc.c, which may lead to remote code execution in certain Python applications that accept floating-point numbers as untrusted input, as demonstrated by a 1e300 argument to c_double.from_param.
This occurs because sprintf is used unsafely.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): Only build and run applications from trusted sources.
Currently no fix is available.

Note: This SSA advises vulnerabilities for firmware version V3.1 only; for versions prior to V3.1 refer to SiemensSecurity Bulletin SSB-439005.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-398330 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-398330.html

https://support.industry.siemens.com/cs/ww/en/view/109478459/

https://www.cisa.gov/news-events/ics-advisories/icsa-23-348-10

Plugin Details

Severity: Critical

ID: 504235

File Name: tenable_ot_siemens_CVE-2021-3177.nasl

Version: 1.3

Type: remote

Family: Tenable.ot

Published: 11/13/2025

Updated: 3/5/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 6.7

CVSS v3

Risk Factor: Critical

Base Score: 9.8

Temporal Score: 8.8

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5, cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 12/12/2023

Vulnerability Publication Date: 12/12/2023

Reference Information

CVE: CVE-2021-3177

CWE: 120

ICSA: 23-348-10