Siemens SIMATIC S7-1500 Insufficient Verification of Data Authenticity (CVE-2021-22947)

medium Tenable OT Security Plugin ID 504179

Synopsis

The remote OT asset is affected by a vulnerability.

Description

When curl >= 7.20.0 and <= 7.78.0 connects to an IMAP or POP3 server to retrieve data using STARTTLS to upgrade to TLS security, the server can respond and send back multiple responses at once that curl caches.
curl would then upgrade to TLS but not flush the in-queue of cached responses but instead continue using and trustingthe responses it got
_before_ the TLS handshake as if they were authenticated.Using this flaw, it allows a Man-In-The-Middle attacker to first inject the fake responses, then pass-through the TLS traffic from the legitimate server and trick curl into sending data back to the user thinking the attacker's injected data comes from the TLS-protected server.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): Only build and run applications from trusted sources.
Currently no fix is available.

Note: This SSA advises vulnerabilities for firmware version V3.1 only; for versions prior to V3.1 refer to SiemensSecurity Bulletin SSB-439005.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-398330 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-389290.pdf

https://cert-portal.siemens.com/productcert/html/ssa-398330.html

https://support.industry.siemens.com/cs/ww/en/view/109478459/

https://support.industry.siemens.com/cs/ww/en/view/109806100/

https://www.cisa.gov/news-events/ics-advisories/icsa-23-348-10

Plugin Details

Severity: Medium

ID: 504179

File Name: tenable_ot_siemens_CVE-2021-22947.nasl

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 11/13/2025

Updated: 2/14/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 4.4

CVSS v3

Risk Factor: Medium

Base Score: 5.9

Temporal Score: 5.3

Vector: CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5, cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 3/8/2022

Vulnerability Publication Date: 3/8/2022

Reference Information

CVE: CVE-2021-22947

CWE: 345

ICSA: 23-348-10