Siemens SIMATIC S7-1500 Improper Neutralization of CRLF Sequences (CVE-2019-9947)

medium Tenable OT Security Plugin ID 504062

Synopsis

The remote OT asset is affected by a vulnerability.

Description

An issue was discovered in urllib2 in Python 2.x through 2.7.16 and urllib in Python 3.x through 3.7.3. CRLF injection is possible if the attacker controls a url parameter, as demonstrated by the first argument to urllib.request.urlopen with \r\n (specifically in the path component of a URL that lacks a ? character) followed by an HTTP header or a Redis command. This is similar to the CVE-2019-9740 query string issue. This is fixed in: v2.7.17, v2.7.17rc1, v2.7.18, v2.7.18rc1; v3.5.10, v3.5.10rc1, v3.5.8, v3.5.8rc1, v3.5.8rc2, v3.5.9;
v3.6.10, v3.6.10rc1, v3.6.11, v3.6.11rc1, v3.6.12, v3.6.9, v3.6.9rc1;
v3.7.4, v3.7.4rc1, v3.7.4rc2, v3.7.5, v3.7.5rc1, v3.7.6, v3.7.6rc1, v3.7.7, v3.7.7rc1, v3.7.8, v3.7.8rc1, v3.7.9.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

Refer to the vendor advisory.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-398330.html

https://support.industry.siemens.com/cs/ww/en/view/109478459/

Plugin Details

Severity: Medium

ID: 504062

Version: 1.1

Type: remote

Family: Tenable.ot

Published: 11/13/2025

Updated: 11/13/2025

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.8

CVSS v3

Risk Factor: Medium

Base Score: 6.1

Temporal Score: 5.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5, cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 12/12/2023

Vulnerability Publication Date: 12/12/2023

Reference Information

CVE: CVE-2019-9947

CWE: 93