Siemens SIMATIC S7-1500 NULL Pointer Dereference (CVE-2025-21864)

medium Tenable OT Security Plugin ID 503917

Synopsis

The remote OT asset is affected by a vulnerability.

Description

In the Linux kernel, the following vulnerability has been resolved:
tcp: drop secpath at the same time as we currently drop dst Xiumei reported hitting the WARN in xfrm6_tunnel_net_exit while running tests that boil down to: - create a pair of netns - run a basic TCP test over ipcomp6 - delete the pair of netns The xfrm_state found on spi_byaddr was not deleted at the time we delete the netns, because we still have a reference on it. This lingering reference comes from a secpath (which holds a ref on the xfrm_state), which is still attached to an skb. This skb is not leaked, it ends up on sk_receive_queue and then gets defer-free'd by skb_attempt_defer_free. The problem happens when we defer freeing an skb (push it on one CPU's defer_list), and don't flush that list before the netns is deleted. In that case, we still have a reference on the xfrm_state that we don't expect at this point. We already drop the skb's dst in the TCP receive path when it's no longer needed, so let's also drop the secpath. At this point, tcp_filter has already called into the LSM hooks that may require the secpath, so it should not be needed anymore. However, in some of those places, the MPTCP extension has just been attached to the skb, so we cannot simply drop all extensions.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens is preparing fixed versions and reports that currently, no fix is available.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-082556 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-082556.html

https://www.cisa.gov/news-events/ics-advisories/icsa-23-348-10

https://www.cisa.gov/news-events/ics-advisories/icsa-25-162-05

Plugin Details

Severity: Medium

ID: 503917

File Name: tenable_ot_siemens_CVE-2025-21864.nasl

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 11/13/2025

Updated: 2/14/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 4.4

CVSS v3

Risk Factor: Medium

Base Score: 5.5

Vector: CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5, cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 6/10/2025

Vulnerability Publication Date: 6/10/2025

Reference Information

CVE: CVE-2025-21864

CWE: 476

ICSA: 23-348-10, 25-162-05