Siemens SIPROTEC 5 Devices Use of Default Credentials (CVE-2024-54015)

high Tenable OT Security Plugin ID 502863

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Affected devices do not properly validate SNMP GET requests. This could allow an unauthenticated, remote attacker to retrieve sensitive information of the affected devices with SNMPv2 GET requests using default credentials.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

- All affected products: Restrict access to port 161/udp to trusted IP addresses only.
- All affected products: Disable the SNMP service running in the communication modules, if not used.
- SIPROTEC 5 7KE85 (CP300), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7ST86 (CP300): Currently no fix is available.
- SIPROTEC 5 Compact 7SX800 (CP050): Update to V9.90 or later version.
- SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP150), SIPROTEC 5 7SK82 (CP150), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SX82 (CP150), SIPROTEC 5 7SY82 (CP150), SIPROTEC 5 7UT82 (CP150):
Update to V9.90 or later version.
- SIPROTEC 5 6MD84 (CP300), SIPROTEC 5 6MD85 (CP300), SIPROTEC 5 6MD86 (CP300), SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 6MU85 (CP300), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ85 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SK85 (CP300), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300), SIPROTEC 5 7SS85 (CP300), SIPROTEC 5 7SX85 (CP300), SIPROTEC 5 7UM85 (CP300), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), SIPROTEC 5 7UT87 (CP300), SIPROTEC 5 7VE85 (CP300), SIPROTEC 5 7VK87 (CP300), SIPROTEC 5 7VU85 (CP300): Update to V9.90 or later version.
- SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.2), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 2), SIPROTEC 5 Communication Module ETH-BD-2FO: Update to V9.90 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-767615 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-767615.html

https://www.cisa.gov/news-events/ics-advisories/icsa-25-044-05

Plugin Details

Severity: High

ID: 502863

File Name: tenable_ot_siemens_CVE-2024-54015.nasl

Version: 1.4

Type: remote

Family: Tenable.ot

Published: 2/20/2025

Updated: 2/14/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:N/A:N

CVSS Score Source: CVE-2024-54015

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.7

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

CVSS v4

Risk Factor: High

Base Score: 8.7

Threat Score: 6.6

Threat Vector: CVSS:4.0/E:U

Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N

Vulnerability Information

CPE: cpe:/o:siemens:siprotec_5_7sa86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ve85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sk85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_compact_7sx800_%28cp050%29_firmware, cpe:/o:siemens:siprotec_5_7sk82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sj81_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7vu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6mu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7st86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7vk87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ke85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7um85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ut82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sy82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7st85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ss85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md84_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md89_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl86_%28cp300%29_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Available: true

Exploit Ease: Exploits are available

Patch Publication Date: 2/11/2025

Vulnerability Publication Date: 2/11/2025

Reference Information

CVE: CVE-2024-54015

CWE: 1392

ICSA: 25-044-05