Rockwellautomation Micrologix Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')

high Tenable.ot Plugin ID 500469
New! Plugin Severity Now Using CVSS v3

The calculated severity for Plugins has been updated to use CVSS v3 by default. Plugins that do not have a CVSS v3 score will fall back to CVSS v2 for calculating severity. Severity display preferences can be toggled in the settings dropdown.

Description

Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.

Solution

Refer to vendor advisory for Security Updates

See Also

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129877/loc/en_US#__highlight

https://us-cert.cisa.gov/ics/advisories/icsa-21-033-01

Plugin Details

Severity: High

ID: 500469

Version: 1.0

Type: local

Family: SCADA

Published: 8/10/2021

Updated: 8/10/2021

Risk Information

CVSS Score Source: CVE-2021-22659

CVSS v2

Risk Factor: High

Base Score: 7.5

Vector: AV:N/AC:L/Au:N/C:P/I:P/A:P

CVSS v3

Risk Factor: High

Base Score: 8.6

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H

Vulnerability Information

CPE: cpe:2.3:o:rockwellautomation:micrologix_1400_firmware:*:*:*:*:*:*:*:*

Patch Publication Date: 3/25/2021

Vulnerability Publication Date: 3/25/2021

Reference Information

CVE: CVE-2021-22659