Synopsis
The remote OT asset is affected by a vulnerability.
Description
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01;
Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.
This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.
Solution
The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.
Siemens provides firmware update V4.27 for EN100 module included in SIPROTEC 4 and SIPROTEC Compact to fix the vulnerabilities. The firmware updates can be found at the following locations on the Siemens website:
http://www.siemens.com/downloads/siprotec-4
http://www.siemens.com/downloads/siprotec-compact
For SIPROTEC Compact 7SJ80 with Ethernet Service Interface on Port A, Siemens provides firmware update V4.76. The firmware update can be found at the following location on the Siemens website:
http://www.siemens.com/downloads/siprotec-compact
An attacker must have network access to the affected devices. For remaining affected products, Siemens recommends to protect network access with appropriate mechanisms (e.g., firewalls, segmentation, VPN). It is advised to configure the environment according to Siemens operational guidelines in order to run the devices in a protected IT environment.
Siemens provides guidance at the following location for operating the devices only within trusted networks:
http://www.siemens.com/gridsecurity
For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location:
http://www.siemens.com/cert/advisories
Plugin Details
Supported Sensors: Tenable OT Security
Risk Information
Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:N/A:N
Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C
Vulnerability Information
CPE: cpe:/o:siemens:siprotec_compact_7sj80_firmware, cpe:/o:siemens:siprotec_compact_7rw80_firmware, cpe:/o:siemens:siprotec_compact_7sj81_firmware, cpe:/o:siemens:siprotec_compact_7sk81_firmware
Required KB Items: Tenable.ot/Siemens
Exploit Ease: No known exploits are available
Patch Publication Date: 5/31/2016
Vulnerability Publication Date: 5/31/2016