Siemens SINEMA Remote Connect Server Multiple Vulnerabilities (SSA-884497)

critical Nessus Plugin ID 131402

Synopsis

The Siemens SINEMA Remote Connect Server is affected by multiple vulnerabilities.

Description

The Siemens SINEMA Remote Connect Server running on the remote host is affected by multiple vulnerabilities:

- The web interface has no means to prevent password guessing attacks. This vulnerability could be exploited by an attacker with network access to the vulnerable software, requiring no privileges and no user interaction. Exploitation could allow full access to the web interface. (CVE-2019-13918)

- Some pages that should only be accessible by a privileged user can also be accessed by a non-privileged user. This vulnerability could be exploited by an attacker with network access and valid credentials for the web interface. No user interaction is required. Exploitation could allow an attacker to access information they should not be able to read. The information affected by this vulnerability does not include passwords.
(CVE-2019-13919)

- Some parts of the web application are not protected against cross-site request forgery (CSRF) attacks. This vulnerability could be exploited by an attacker who is able to trigger requests of a logged-in user to the application. Exploitation could allow switching the connectivity state of a user or a device.
(CVE-2019-13920)

- An attacker with administrative privileges can obtain the hash of a connected device’s password. The security vulnerability could be exploited by an attacker with network access to the SINEMA Remote Connect Server and administrative privileges. (CVE-2019-13922)

Solution

Update to V2.0 SP1 or later.

See Also

http://www.nessus.org/u?7cc38551

https://www.us-cert.gov/ics/advisories/icsa-19-260-02

Plugin Details

Severity: Critical

ID: 131402

File Name: scada_siemens_sinemarc_ssa-884497.nbin

Version: 1.67

Type: remote

Family: SCADA

Published: 12/2/2019

Updated: 4/23/2024

Supported Sensors: Nessus

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v2

Risk Factor: High

Base Score: 7.5

Temporal Score: 5.5

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P

CVSS Score Source: CVE-2019-13918

CVSS v3

Risk Factor: Critical

Base Score: 9.8

Temporal Score: 8.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: x-cpe:/a:siemens:sinema_remote_connect_server

Required KB Items: installed_sw/Siemens SINEMA Remote Connect Server

Exploit Ease: No known exploits are available

Patch Publication Date: 9/10/2019

Vulnerability Publication Date: 9/10/2019

Reference Information

CVE: CVE-2019-13918, CVE-2019-13919, CVE-2019-13920, CVE-2019-13922

ICSA: 19-260-02