CVE-2026-3611

critical

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

References

https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03

https://www.honeywell.com/us/en/contact

https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json

Details

Source: Mitre, NVD

Published: 2026-03-12

Updated: 2026-03-12

Risk Information

CVSS v2

Base Score: 10

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:C/A:C

Severity: Critical

CVSS v3

Base Score: 10

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

Severity: Critical

CVSS v4

Base Score: 10

Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H

Severity: Critical