Description

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

References

https://thecyberexpress.com/microsoft-rce-dos-exploits-found-in-rockwell/?&web_view=true

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724

Details

Source: Mitre, NVD

Published: 2023-09-12

Updated: 2026-06-17

Risk Information

CVSS v2

Base Score: 10

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:C/A:C

Severity: Critical

CVSS v3

Base Score: 9.8

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Severity: Critical

EPSS

EPSS: 0.10974