CVE-2021-32986

critical

Description

After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.

References

https://www.cisa.gov/uscert/ics/advisories/icsa-21-166-02

Details

Source: Mitre, NVD

Published: 2022-04-04

Updated: 2022-10-25

Risk Information

CVSS v2

Base Score: 7.5

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P

Severity: High

CVSS v3

Base Score: 9.8

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Severity: Critical

EPSS

EPSS: 0.0006