CVE-2019-13553

critical

Description

Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.

References

https://www.us-cert.gov/ics/advisories/icsa-19-297-01

http://seclists.org/fulldisclosure/2019/Oct/45

Details

Source: Mitre, NVD

Published: 2019-10-25

Updated: 2026-06-17

Risk Information

CVSS v2

Base Score: 10

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:C/A:C

Severity: Critical

CVSS v3

Base Score: 9.8

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Severity: Critical

EPSS

EPSS: 0.00184