Siemens SIMATIC S7-1500 Use After Free (CVE-2023-4806)

medium Tenable OT Security Plugin ID 503946

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A flaw was found in glibc. In an extremely rare situation, the getaddrinfo function may access memory that has been freed, resulting in an application crash. This issue is only exploitable when a NSS module implements only the _nss_*_gethostbyname2_r and
_nss_*_getcanonname_r hooks without implementing the
_nss_*_gethostbyname3_r hook. The resolved name should return a large number of IPv6 and IPv4, and the call to the getaddrinfo function should have the AF_INET6 address family with AI_CANONNAME, AI_ALL and AI_V4MAPPED as flags.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): Only build and run applications from trusted sources.
Currently no fix is available.
- SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): Only build and run applications from trusted sources.
Currently no fix is available.

Note: This SSA advises vulnerabilities for firmware version V3.1 only; for versions prior to V3.1 refer to SiemensSecurity Bulletin SSB-439005.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-398330 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-082556.html

https://support.industry.siemens.com/cs/ww/en/view/109945851/

https://www.cisa.gov/news-events/ics-advisories/icsa-23-348-10

Plugin Details

Severity: Medium

ID: 503946

File Name: tenable_ot_siemens_CVE-2023-4806.nasl

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 11/13/2025

Updated: 2/27/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 4.4

CVSS v3

Risk Factor: Medium

Base Score: 5.9

Vector: CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5, cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 6/13/2023

Vulnerability Publication Date: 6/13/2023

Reference Information

CVE: CVE-2023-4806

CWE: 416

ICSA: 23-348-10