Siemens SIPROTEC 5 Products Files or Directories Accessible to External Parties (CVE-2024-53649)

high Tenable OT Security Plugin ID 502812

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Affected devices do not properly limit the path accessible via their webserver. This could allow an authenticated remote attacker to read arbitrary files from the filesystem of affected devices.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

- SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 7SA82 (CP100), SIPROTEC 5 7SD82 (CP100), SIPROTEC 5 7SJ81 (CP100), SIPROTEC 5 7SJ82 (CP100), SIPROTEC 5 7SK82 (CP100), SIPROTEC 5 7SL82 (CP100), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7UT82 (CP100):
Currently no fix is available
- SIPROTEC 5 Compact 7SX800 (CP050): Update to V9.80 or later version
- SIPROTEC 5 6MD84 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300) and SIPROTEC 5 7VK87 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP150), and SIPROTEC 5 7SJ85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SK82 (CP150) and SIPROTEC 5 7SK85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7ST86 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SX82 (CP150) and SIPROTEC 5 7SX85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SY82 (CP150): Update to V9.80 or later version
- SIPROTEC 5 7UT82 (CP150), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), and SIPROTEC 5 7UT87 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7VU85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 6MD85 (CP300) and SIPROTEC 5 6MD86 (CP300): Update to V9.80 or later version
- : Update to V9.80 or later version
- SIPROTEC 5 6MU85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7KE85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7SS85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7UM85 (CP300): Update to V9.80 or later version
- SIPROTEC 5 7VE85 (CP300): Update to V9.80 or later version

Siemens recommends operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN).
It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.

Recommended security guidelines can be found here.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-194557 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-194557.html

https://www.cisa.gov/news-events/ics-advisories/icsa-25-016-04

Plugin Details

Severity: High

ID: 502812

File Name: tenable_ot_siemens_CVE-2024-53649.nasl

Version: 1.5

Type: remote

Family: Tenable.ot

Published: 1/20/2025

Updated: 2/14/2026

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: Medium

Base Score: 6.8

Temporal Score: 5

Vector: CVSS2#AV:N/AC:L/Au:S/C:C/I:N/A:N

CVSS Score Source: CVE-2024-53649

CVSS v3

Risk Factor: Medium

Base Score: 6.5

Temporal Score: 5.7

Vector: CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

CVSS v4

Risk Factor: High

Base Score: 7.1

Threat Score: 4.9

Threat Vector: CVSS:4.0/E:U

Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N

Vulnerability Information

CPE: cpe:/o:siemens:siprotec_5_7sa86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ve85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sk82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7sk85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_compact_7sx800_%28cp050%29_firmware, cpe:/o:siemens:siprotec_5_7sk82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sj81_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7vu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7ut86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6mu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7st86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7sd82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7sd86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sj82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7vk87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ke85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7um85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ut82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sy82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sa82_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7st85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj81_%28cp100%29_firmware, cpe:/o:siemens:siprotec_5_7sj85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ss85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md84_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md89_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl86_%28cp300%29_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 1/14/2025

Vulnerability Publication Date: 1/14/2025

Reference Information

CVE: CVE-2024-53649

CWE: 552

ICSA: 25-016-04