Siemens RUGGEDCOM ROX Execution with Unnecessary Privileges (CVE-2021-37174)

high Tenable OT Security Plugin ID 501635

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.14.1), RUGGEDCOM ROX RX1400 (All versions < V2.14.1), RUGGEDCOM ROX RX1500 (All versions < V2.14.1), RUGGEDCOM ROX RX1501 (All versions < V2.14.1), RUGGEDCOM ROX RX1510 (All versions < V2.14.1), RUGGEDCOM ROX RX1511 (All versions < V2.14.1), RUGGEDCOM ROX RX1512 (All versions < V2.14.1), RUGGEDCOM ROX RX1524 (All versions < V2.14.1), RUGGEDCOM ROX RX1536 (All versions < V2.14.1), RUGGEDCOM ROX RX5000 (All versions < V2.14.1). The affected devices have a privilege escalation vulnerability, if exploited, an attacker could gain root user access.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has released an update and recommends users update to v2.14.1 or later version.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

- Apply the principle of least privileges for accounts configured on the affected devices.

As a general security measure, Siemens strongly recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens’ operational guidelines for industrial security and follow the recommendations in the product manuals.

Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity

For more information about this issue, please see Siemens Security Advisory SSA-150692

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-150692.pdf

https://www.cisa.gov/news-events/ics-advisories/icsa-21-259-01

Plugin Details

Severity: High

ID: 501635

Version: 1.5

Type: remote

Family: Tenable.ot

Published: 9/14/2023

Updated: 3/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v2

Risk Factor: High

Base Score: 9

Temporal Score: 6.7

Vector: CVSS2#AV:N/AC:L/Au:S/C:C/I:C/A:C

CVSS Score Source: CVE-2021-37174

CVSS v3

Risk Factor: High

Base Score: 8.8

Temporal Score: 7.7

Vector: CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:ruggedcom_rox_mx5000_firmware, cpe:/o:siemens:ruggedcom_rox_rx1400_firmware, cpe:/o:siemens:ruggedcom_rox_rx1500_firmware, cpe:/o:siemens:ruggedcom_rox_rx1501_firmware, cpe:/o:siemens:ruggedcom_rox_rx1510_firmware, cpe:/o:siemens:ruggedcom_rox_rx1511_firmware, cpe:/o:siemens:ruggedcom_rox_rx1512_firmware, cpe:/o:siemens:ruggedcom_rox_rx1524_firmware, cpe:/o:siemens:ruggedcom_rox_rx1536_firmware, cpe:/o:siemens:ruggedcom_rox_rx5000_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 9/14/2021

Vulnerability Publication Date: 9/14/2021

Reference Information

CVE: CVE-2021-37174

CWE: 250