7-Technologies IGSS < 10.0.0 ODBC Buffer Overflow RCE

This script is Copyright (C) 2016-2017 Tenable Network Security, Inc.


Synopsis :

The remote host contains a SCADA application that is affected by a
remote code execution vulnerability.

Description :

The 7-Technologies / Schneider-Electric Interactive Graphical SCADA
System (IGSS) application installed on the remote Windows host is a
version prior to 10.0.0. It is, therefore, affected by a stack-based
buffer overflow condition in the ODBC service due to improper
sanitization of user-supplied input. An unauthenticated, remote
attacker can exploit this, via a crafted packet sent to TCP port
22202, to cause a denial of service or to execute arbitrary code with
administrative privileges.

See also :

https://ics-cert.us-cert.gov/advisories/ICSA-11-119-01

Solution :

Upgrade to IGSS version 10.0.0 or later.

Risk factor :

Critical / CVSS Base Score : 10.0
(CVSS2#AV:N/AC:L/Au:N/C:C/I:C/A:C)

Family: SCADA

Nessus Plugin ID: 89031 ()

Bugtraq ID: 78437

CVE ID: CVE-2011-2959

Ready to Amp Up Your Nessus Experience?

Get Nessus Professional to scan unlimited IPs, run compliance checks & more

Buy Nessus Professional Now