Ecava IntegraXor ActiveX save Method Buffer Overflow

high Nessus Plugin ID 51360

Synopsis

The remote Windows host has an ActiveX control affected by a buffer overflow vulnerability.

Description

The version of the IntegraXor.Project ActiveX control installed on the remote Windows host contains a stack-based buffer overflow that can be triggered by passing a value larger than 1024 bytes to its 'save()' method.

Successful exploitation of this vulnerability can cause a crash in the associated browser and may allow for arbitrary code execution.

Solution

Upgrade to version 3.5 (Build 3900.10) or later.

See Also

http://www.nessus.org/u?0e87f17c

Plugin Details

Severity: High

ID: 51360

File Name: scada_integraxor_activex_save_bof.nbin

Version: 1.217

Type: local

Family: SCADA

Published: 12/22/2010

Updated: 4/23/2024

Supported Sensors: Nessus

Risk Information

VPR

Risk Factor: Medium

Score: 6.7

CVSS v2

Risk Factor: High

Base Score: 9.3

Temporal Score: 8.8

Vector: CVSS2#AV:N/AC:M/Au:N/C:C/I:C/A:C

Vulnerability Information

Required KB Items: SCADA/Apps/Ecava/IntegraXor/Installed

Exploit Available: true

Exploit Ease: Exploits are available

Patch Publication Date: 10/14/2010

Vulnerability Publication Date: 12/18/2010

Reference Information

CVE: CVE-2010-4597

BID: 45487

CERT: 603928

ICS-ALERT: 10-322-01